Chilled water piping(≥5℃)

Flexible foam rubber pipe shell (mm) Glass wool pipe shell (mm)
Pipe nominal diameter Thickness Pipe nominal diameter Thickness
Inside the ceiling of the room, the machine room 15~25 25 15~25 25
32~80 30 32~80 30
≥100 35 ≥100 35
Outdoor 15~25 35 15~25 30
32~80 40 32~80 35
≥100 50 ≥100 40

Hot water, hot and cold combined pipe (5~60℃)

Flexible foam rubber pipe shell (mm) Glass wool pipe shell (mm)
Pipe nominal diameter Thickness Pipe nominal diameter Thickness
Inside the ceiling of the room, the machine room ≤50 30 ≤40 35
70~150 30 50~100 40
≥200 35 125~250 45
≥300 50
Outdoor ≤50 35 ≤40 40
70~150 35 50~100 45
≥200 40 125~250 50
≥300 55

Hot water, hot and cold combined pipe (0~95℃)

Polyurethane rigid foam (direct burial) (mm) Glass wool pipe shell (mm)
Pipe nominal diameter Thickness Pipe nominal diameter Thickness
Inside the ceiling of the room, the machine room ≤32 30 ≤50 50
40~200 35 70~150 60
≥250 45 ≥200 70
Outdoor ≤32 35 ≤50 60
40~200 40 70~150 70
≥250 50 ≥200 80

Ice storage pipes (≥ -10°C)

Pipe nominal diameter Flexible foam rubber (mm) Polyurethane foam (mm)
Indoor 15~40 35 30
50~100 40 40
≥125 50 50
PHE (Plate heat exchanger) 35
Tanks 60 50
Outdoor 15~40 40 40
50~100 50 50
≥125 60 60
Tanks 70 70

Air conditioning condensate piping

Flexible foam rubber pipe shell (mm) Glass wool pipe shell (mm)
Inside the ceiling of air-conditioned rooms 10 10
Non-air-conditioned rooms 15 15

Air conditioning air ducts

Flexible foam rubber pipe shell (mm) Glass wool board, felt (mm)
Air supply temperature≥14℃ Non-air-conditioned rooms 20 40
In air-conditioned rooms 20 30
Air supply temperature≥4℃ Non-air-conditioned rooms 25 50
In air-conditioned rooms 25 40

Refrigerant piping (split air conditioner, VRV)

Installation Instructions Minimum thickness of the required insulation
Through the air-conditioned space 19mm
Through unconditioned spaces 19mm
Throughout the bathroom ceiling space 25mm