Temperatura

Refrigerante

° F° CR-22R-410aR-407cR-134aR-404a
-60-51,111.90.91621.6-
-55-48,39.21,813.720,2-
-50-45,66.14.311.118.6-
-45-42,82.778.116,7-
-40-400.610.14,814.74.9
-35-37,22.613.51,112.37,5
-30-34,44.917.21,59.710.3
-25-31,77,521.43.76,813.5
-20-28,910.225.96.23.616.8
-18-27,811.427,87.22,218.3
-16-26,712,629,78.40.719.8
-14-25,613.931.89,50.421.3
-12-24,415.233.910.71.222.9
-10-23,316.536.111.9224.6
-8-22,217.938.413.22.826,3
-6-21,119.440,714.63.728
-4-2020.943.115,94,629,8
-2-18,922.445,617.45,531.7
0-17,82448.218.96,533,7
1-17,224,849,519.6734,7
2-16,725,750,920.47,535,7
3-16,126,552.221,2836,7
4-15,627.453,6228.637,7
5-1528.35522,89.138,8
6-14,429.156,423.79.739,8
7-13,93057,924,510.240,9
8-13,33159.325.410,842
9-12,831,960,826.211.443.1
10-12,232,862.327.11244.3
11-11,733,863,92812,645.4
12-11,134,865,42913.246,6
13-10,635,86729.913.847,8
14-1036,868,630.914.449
15-9,437,870.231.815.150.2
16-8,938,871,932,815.751,5
17-8,339,973,533,816.452,7
18-7,840,975.234,817.154
19-7,2427735,917.755.3
20-6,743.178,736,918,456,6
21-6,144.280,53819.257,9
22-5,645.382.339.119.959.3
23-546,584.140.220.660,6
24-4,447,685,941.321.462
25-3,948,887,842.422.163,4
26-3,35089,743,622.964,8
27-2,851,291,644,723.766.2
28-2,252.493,545,924,567,7
29-1,753,795,547.125,369.2
30-1,154,997,548,426.170,7
31-0,656.299,549,626.972,1
32057,5101.650,927,873,8
330.658,8103.652.128.675,3
341,160.2105,753.429,576,9
351.761,5107.954,830.478,5
362,262,911056.131.380.2
372.864,3112.257,532,281,7
383.365,7114.458,933.183,5
393.967.1116,760,334.185.2
404.468,6118,961,73586,9
41570121.263.13688,6
425,671,5123,664,63790,4
436.173125,966.13892.2
446.774,5128,367,63994
457.276.1130,769.14095,8
467,877,6133.270,641.197,6
478.379.2135,672.242,299,5
488.980,8138.273,843.2101.4
499.482,4140,775,444.3103.3
501084.1143,3177.145.4105.3
5512.892,6156,610651,2115.3
6015.6101.6170,7116.257,4126
6518.311.3185,712764137,4
7021.1121,5201.5138,571.1149,3
7523.9132.2218.2150,678,6161,9
8026,7143,7235,9163,586,7175,4
8529.4155,7254,617795,2189,6
9o[32,2168,4274,3191,3104.3204,5
9535181,9295206.4113,9220.2
10037,8196316,922.3.124.1236,8
10540,6210,8339,9239134,9254.2
11043.3226,4364.1256,5146,3272,5
11546.1242,8289,6274,9158,4291,9
12048,9260416.4294,2171.1312.1
12551,7278.1444,5314,5184,533.4
13054.4297474335,7198,7355,6
13557.2316,7505357,8213,5379,1
14060337,4537,6380,9229.2403.7
14562,8359,1571,7405.1245,6429,6
15065,6381,7607,6430,3262,8456,8
15568.3405.4645,2456,6281484,8

Os pontos de dados são reproduzidos com base nas informações disponíveis. Nós (SCY Chiller) não assumimos nenhuma responsabilidade por erros de dados.

Baixar este gráfico aqui.

2 pensamentos "Tabela de Temperatura-Pressão de Refrigerantes para R-22, R-410A, R-407C, R134A, R404A"

  1. Júlio Campos diz:

    Oi Leo.
    Qual a pressão manométrica para o gás r404a em um liofilizador que trabalha com temperatura de -60ºC?

    • Leão diz:

      Para o refrigerante R404a a uma temperatura de -60ºC, a pressão correspondente está normalmente abaixo da sua faixa operacional normal. Para saber o valor exato deve consultar a tabela pressão-temperatura (PT) específica do R404a. Atualmente não temos esses dados em mãos. No entanto, lembre-se de que operar em temperaturas tão baixas pode exigir equipamento especializado.

Deixe uma resposta

Seu endereço de e-mail não será publicado. Os campos obrigatórios estão marcados *