Temperatur

Kältemittel

° F.° C.R-22R-410aR-407cR-134aR-404a
-60-51,111.90.91621.6
-55-48,39.21.813.720.2
-50-45,66.14.311.118.6
-45-42,82.778.116.7
-40-400.610.14.814.74.9
-35-37,22.613.51.112.37.5
-30-34,44.917.21.59.710.3
-25-31.77.521.43.76.813.5
-20-28.910.225.96.23.616.8
-18-27.811.427.87.22.218.3
-16-26.712.629.78.40.719.8
-14-25.613.931.89.50.421.3
-12-24.415.233.910.71.222.9
-10-23.316.536.111.9224.6
-8-22.217.938.413.22.826.3
-6-21.119.440.714.63.728
-4-2020.943.115.94.629.8
-2-18.922.445.617.45.531.7
0-17.82448.218.96.533.7
1-17.224.849,519.6734.7
2-16.725.750.920.47.535.7
3-16.126.552.221.2836.7
4-15.627.453,6228.637.7
5-1528.35522.89.138.8
6-14.429.156.423.79.739.8
7-13.93057.924.510.240.9
8-13.33159.325.410.842
9-12.831.960,826.211.443.1
10-12.232.862.327.11244.3
11-11.733.863,92812.645.4
12-11.134.865,42913.246.6
13-10.635.86729.913.847,8
14-1036.868,630.914.449
15-9.437.870.231.815.150.2
16-8.938.871.932.815.751,5
17-8.339.973,533.816.452,7
18-7,840.975,234.817.154
19-7.2427735.917.755.3
20-6,743.178,736.918.456,6
21-6.144.280,53819.257.9
22-5.645.382,339.119.959.3
23-546,584.140.220.660.6
24-4.447,685,941.321.462
25-3,948,887,842.422.163,4
26-3.35089,743,622.964,8
27-2,851.291,644.723.766.2
28-2.252.493,545.924.567,7
29-1,753,795,547.125.369.2
30-1.154.997,548.426.170,7
31-0,656.299,549,626.972.1
32057,5101,650.927.873,8
330.658,8103,652.128.675,3
341.160.2105,753.429.576,9
351.761,5107,954,830.478,5
362.262,911056.131.380.2
372.864.3112.257,532.281,7
383.365,7114.458.933.183,5
393.967.1116,760.334.185,2
404.468,6118,961,73586,9
41570121.263.13688,6
425.671,5123,664,63790,4
436.173125,966.13892,2
446.774,5128.367,63994
457.276.1130,769.14095,8
467.877,6133.270.641.197,6
478.379,2135,672.242.299,5
488.980,8138.273,843.2101.4
499.482,4140,775,444.3103.3
501084.1143,3177.145.4105.3
5512.892,6156,610651.2115.3
6015.6101,6170,7116.257.4126
6518.311.3185,712764137,4
7021.1121,5201.5138,571.1149,3
7523.9132.2218.2150,678,6161,9
8026.7143,7235,9163,586,7175,4
8529.4155,7254,617795,2189,6
9o[32.2168,4274,3191,3104.3204,5
9535181,9295206.4113,9220.2
10037.8196316,922.3.124.1236,8
10540.6210.8339,9239134,9254,2
11043.3226,4364.1256,5146,3272,5
11546.1242,8289,6274,9158,4291,9
12048.9260416,4294.2171.1312.1
12551.7278.1444,5314,5184,533.4
13054.4297474335,7198,7355,6
13557.2316,7505357,8213,5379.1
14060337,4537,6380,9229.2403,7
14562,8359.1571,7405.1245,6429,6
15065,6381,7607.6430.3262,8456,8
15568,3405.4645,2456,6281484,8

Datenpunkte werden basierend auf verfügbaren Informationen reproduziert. Wir (SCY Chiller) übernehmen keine Verantwortung oder Haftung für Datenfehler.

Laden Sie dieses Diagramm herunter Hier.

2 Meinungen zu “Kältemittel-Temperatur-Druck-Diagramm für R-22, R-410A, R-407C, R134A, R404A

  1. Julio Campos sagt:

    Hallo Leo.
    Wie hoch ist der Manometerdruck für R404a-Gas in einem Gefriertrockner, der bei einer Temperatur von -60 °C arbeitet?

    • Löwe sagt:

      Für das Kältemittel R404a liegt der entsprechende Druck bei einer Temperatur von -60 °C typischerweise unter seinem üblichen Betriebsbereich. Um den genauen Wert zu ermitteln, sollten Sie das für R404a spezifische Druck-Temperatur-Diagramm (PT) konsultieren. Derzeit liegen uns keine derartigen Daten vor. Bedenken Sie jedoch, dass für den Betrieb bei solch niedrigen Temperaturen möglicherweise spezielle Ausrüstung erforderlich ist.

Hinterlasse eine Antwort

Deine Email-Adresse wird nicht veröffentlicht. erforderliche Felder sind markiert *