درجة الحرارة

المبرد

درجة فهرنهايتدرجة مئويةآر - 22R-410aR-407cآر - 134 أR-404a
-60-51.111.90.91621.6-
-55-48.39.21.813.720.2-
-50-45.66.14.311.118.6-
-45-42.82.778.116.7-
-40-400.610.14.814.74.9
-35-37.22.613.51.112.37.5
-30-34.44.917.21.59.710.3
-25-31.77.521.43.76.813.5
-20-28.910.225.96.23.616.8
-18-27.811.427.87.22.218.3
-16-26.712.629.78.40.719.8
-14-25.613.931.89.50.421.3
-12-24.415.233.910.71.222.9
-10-23.316.536.111.9224.6
-8-22.217.938.413.22.826.3
-6-21.119.440.714.63.728
-4-2020.943.115.94.629.8
-2-18.922.445.617.45.531.7
0-17.82448.218.96.533.7
1-17.224.849.519.6734.7
2-16.725.750.920.47.535.7
3-16.126.552.221.2836.7
4-15.627.453.6228.637.7
5-1528.35522.89.138.8
6-14.429.156.423.79.739.8
7-13.93057.924.510.240.9
8-13.33159.325.410.842
9-12.831.960.826.211.443.1
10-12.232.862.327.11244.3
11-11.733.863.92812.645.4
12-11.134.865.42913.246.6
13-10.635.86729.913.847.8
14-1036.868.630.914.449
15-9.437.870.231.815.150.2
16-8.938.871.932.815.751.5
17-8.339.973.533.816.452.7
18-7.840.975.234.817.154
19-7.2427735.917.755.3
20-6.743.178.736.918.456.6
21-6.144.280.53819.257.9
22-5.645.382.339.119.959.3
23-546.584.140.220.660.6
24-4.447.685.941.321.462
25-3.948.887.842.422.163.4
26-3.3هذا المبرد التجاري مناسب للمباني السكنية والتجارية ، ويمكن أن يعمل بشكل مثالي مع نظام HVAC.89.743.622.964.8
27-2.851.291.644.723.766.2
28-2.252.493.545.924.567.7
29-1.753.795.547.125.369.2
30-1.154.997.548.426.170.7
31-0.656.299.549.626.972.1
32057.5101.650.927.873.8
330.658.8103.652.128.675.3
40HP مبرد مياه معبأة 11.160.2105.753.429.576.9
351.761.5107.954.830.478.5
362.262.911056.131.380.2
372.864.3112.257.532.281.7
383.365.7114.458.933.183.5
393.967.1116.760.334.185.2
404.468.6118.961.73586.9
41570121.263.13688.6
425.671.5123.664.63790.4
436.173125.966.13892.2
446.774.5128.367.63994
457.276.1130.769.14095.8
467.877.6133.270.641.197.6
478.379.2135.672.242.299.5
488.980.8138.273.843.2101.4
499.482.4140.775.444.3103.3
هذا المبرد التجاري مناسب للمباني السكنية والتجارية ، ويمكن أن يعمل بشكل مثالي مع نظام HVAC.1084.1143.3177.145.4105.3
5512.892.6156.610651.2115.3
6015.6101.6170.7116.257.4126
6518.311.3185.712764137.4
7021.1121.5201.5138.571.1149.3
7523.9132.2218.2150.678.6161.9
8026.7143.7235.9163.586.7175.4
8529.4155.7254.617795.2189.6
9o[32.2168.4274.3191.3104.3204.5
9535181.9295206.4113.9220.2
10037.8196316.922.3.124.1236.8
10540.6210.8339.9239134.9254.2
11043.3226.4364.1256.5146.3272.5
11546.1242.8289.6274.9158.4291.9
12048.9260416.4294.2171.1312.1
12551.7278.1444.5314.5184.533.4
13054.4297474335.7198.7355.6
13557.2316.7505357.8213.5379.1
14060337.4537.6380.9229.2403.7
14562.8359.1571.7405.1245.6429.6
15040HP مبرد مياه معبأة 1381.7607.6430.3262.8456.8
15568.3405.4645.2456.6281484.8

يتم استنساخ نقاط البيانات على أساس المعلومات المتاحة. نحن (SCY Chiller) لا نتحمل أي مسؤولية أو التزام تجاه أخطاء البيانات.

قم بتنزيل هذا المخطط هنا.

تعليقان اثنان على “مخطط ضغط درجة حرارة المبردات لـ R-22 ، R-410A ، R-407C ، R134A ، R404A

  1. خوليو كامبوس يقول:

    مرحبًا ليو.
    ما هو مقياس الضغط للغاز r404a في مجفف التجميد الذي يعمل عند درجة حرارة -60 درجة مئوية؟

    • ليو يقول:

      بالنسبة لغاز التبريد R404a عند درجة حرارة -60 درجة مئوية، يكون الضغط المقابل عادةً أقل من نطاق التشغيل المعتاد. للعثور على القيمة الدقيقة، يجب عليك الرجوع إلى مخطط درجة حرارة الضغط (PT) الخاص بـ R404a. ليس لدينا حاليا مثل هذه البيانات في متناول اليد. ومع ذلك، تذكر أن العمل في درجات الحرارة المنخفضة هذه قد يتطلب معدات متخصصة.

اترك رد

لن يتم نشر عنوان بريدك الإلكتروني. الحقول المطلوبة محددة *