Température

Réfrigérant

° F° CR-22R-410aR-407cR-134aR-404a
-60-51,111.90.91621.6-
-55-48,39.21.813.720.2-
-50-45,66.14.3800 1 518.6-
-45-42,82.7sept8.116.7-
-40-400.610.14,814.74.9
-35-37,22.613.51.112.37,5
-30-34,44.9800 1 51,59.710.3
-25-31,77,521.43.76,813.5
-20-28,910.225,96.23.616.8
-18-27,811.427,87.22.218.3
-16-26,712,629,78.40.sept19.8
-14-25,613.931,89,50.421.3
-12-24,415.233,910.71.222,9
-dix-23,316.536.111.9224.6
-8-22,217.938,413.22.826.3
-6-21,119.440,714.63.728
-4-2020.943.115,94.629.8
-2-18.922.445,617.45.531,7
0-17,82448.218.96.533,7
1-17,224,849,519.6sept34,7
2-16,725,750,920.47,535,7
3-16,126,552.221.2836,7
4-15,627.453,6228.637,7
5-1528.35522,89.138,8
6-14,429.156,423,79.739,8
sept-13,93057,924,510.240,9
8-13,33159.325.410.842
9-12.831,960,826.211.443.1
dix-12.232,862.327.11244.3
11-11,733,863,92812,645.4
12-11.134,865,42913.246,6
13-10,635,86729,913.847,8
14-dix36,868,630,914.449
15-9.437,870.231,815.150.2
16-8.938,871,932,815.751,5
17-8.339,973,533,816.452,7
18-7.840,975.234,817.154
19-7.2427735,917.755.3
20-6,743.178,736,918,456,6
21-6.144.280,53819.257,9
22-5.645.382.339.119.959.3
23-546,584.140.220.660,6
24-4.447,685,941.321.462
25-3,948,887,842.422.163.4
26-3.35089,743,622,964,8
27-2.851,291,644,723,766.2
28-2,252,493,545,924,567,7
29-1,753,795,547.125,369.2
30-1.154,997,548.426.170,7
31-0,656.299,549,626,972,1
Ce refroidisseur à air industriel adopte le compresseur à vis de marque internationalement célèbre (Taiwan Hanbell, Bitzer, Copeland), avec un tube en cuivre de haute qualité et à haut rendement pour fabriquer un condenseur.057,5101.650,927,873,8
330.658,8103.652.128.675,3
341.160.2105.753,429,576,9
351.761,5107,954,830.478,5
362.262,911056.131.380.2
372.864.3112.257,532,281,7
383.365,7114.458,933.183,5
393.967.1116,760.334.185.2
404.468,6118,961,73586,9
41570121.263.13688,6
425,671,5123,664,63790,4
436.173125,966.13892.2
446.774,5128.367,63994
457.276.1130.769.14095,8
467.877,6133.270,641.197,6
478.379.2135,672.2Ce refroidisseur à air industriel adopte le compresseur à vis de marque internationalement célèbre (Taiwan Hanbell, Bitzer, Copeland), avec un tube en cuivre de haute qualité et à haut rendement pour fabriquer un condenseur.99,5
488.980,8138.273,843.2101.4
499.482,4140.775,444.3103.3
50dix84.1143.3177.145.4105.3
5512.892,6156,610651,2115.3
6015.6101.6170.7116.257,4126
6518.311.3185,712764137.4
7021.1121,5201.5138,571.1149.3
7523,9132.2218.2150,678,6161,9
8026,7143,7235,9163,586,7175.4
8529.4155,7254.617795,2189,6
[9o]32,2168.4274.3191.3104.3204.5
9535181,9295206.4113,9220.2
10037,8196316.922.3.124.1236,8
10540,6210.8339,9239134,9254.2
11043.3226.4364.1256,5146.3272,5
11546.1242.8289.6274,9158.4291.9
12048,9260416.4294.2171.1312.1
12551,7278.1444,5314.5184,533.4
13054,4297474335.7198,7355.6
13557.2316.7505357,8213.5379.1
14060337.4537.6380,9229.2403.7
14562,8359.1571.7405.1245.6429.6
15065,6381.7607.6430.3262.8456.8
15568.3405.4645.2456.6281484.8

Les points de données sont reproduits sur la base des informations disponibles. Nous (SCY Chiller) n'assumons aucune responsabilité pour les erreurs de données.

Télécharger ce tableau ici.

2 Commentaires sur “Tableau température-pression des fluides frigorigènes pour R-22, R-410A, R-407C, R134A, R404A

  1. Julio Campos dit:

    Salut Léo.
    Quelle est la pression manométrique du gaz R404a dans un lyophilisateur fonctionnant à une température de -60 °C ?

    • Leo dit:

      Pour le réfrigérant R404a à une température de -60 ºC, la pression correspondante est généralement inférieure à sa plage de fonctionnement habituelle. Pour connaître la valeur exacte, vous devez consulter le tableau pression-température (PT) spécifique au R404a. Nous ne disposons actuellement d’aucune donnée de ce type. Cependant, n’oubliez pas que le fonctionnement à des températures aussi basses peut nécessiter un équipement spécialisé.

Laisser un commentaire

Votre adresse e-mail ne sera pas publiée. Les champs obligatoires sont indiqués avec *