La temperatura | Refrigerante | |||||
° F | ° C | R-22 | R-410a | R-407c | R-134a | R-404a |
-60 | -51,1 | 11.9 | 0.9 | dieciséis | 21.6 | - |
-55 | -48,3 | 9.2 | 1.8 | 13.7 | 20,2 | - |
-50 | -45,6 | 6.1 | 4.3 | 11,1 | 18.6 | - |
-45 | -42.8 | 2.7 | 7 | 8.1 | 16,7 | - |
-40 | -40 | 0.6 | 10.1 | 4.8 | 14.7 | 4.9 |
-35 | -37.2 | 2.6 | 13.5 | 1.1 | 12.3 | 7.5 |
-30 | -34.4 | 4.9 | 17.2 | 1,5 | 9.7 | 10.3 |
-25 | -31.7 | 7.5 | 21.4 | 3.7 | 6,8 | 13.5 |
-20 | -28,9 | 10.2 | 25,9 | 6.2 | 3.6 | 16.8 |
-18 | -27,8 | 11.4 | 27,8 | 7.2 | 2.2 | 18.3 |
-dieciséis | -26,7 | 12,6 | 29.7 | 8.4 | 0.7 | 19.8 |
-14 | -25,6 | 13.9 | 31.8 | 9.5 | 0.4 | 21.3 |
-12 | -24,4 | 15.2 | 33,9 | 10.7 | 1.2 | 22,9 |
-10 | -23,3 | 16.5 | 36.1 | 11.9 | 2 | 24.6 |
-8 | -22.2 | 17.9 | 38.4 | 13.2 | 2.8 | 26.3 |
-6 | -21.1 | 19.4 | 40.7 | 14.6 | 3.7 | 28 |
-4 | -20 | 20,9 | 43.1 | 15,9 | 4.6 | 29.8 |
-2 | -18,9 | 22.4 | 45.6 | 17.4 | 5.5 | 31.7 |
0 | -17.8 | 24 | 48.2 | 18.9 | 6.5 | 33.7 |
1 | -17.2 | 24,8 | 49.5 | 19.6 | 7 | 34.7 |
2 | -16.7 | 25.7 | 50,9 | 20.4 | 7.5 | 35.7 |
3 | -16.1 | 26.5 | 52.2 | 21,2 | 8 | 36.7 |
4 | -15,6 | 27.4 | 53.6 | 22 | 8.6 | 37.7 |
5 | -15 | 28.3 | 55 | 22.8 | 9.1 | 38.8 |
6 | -14.4 | 29.1 | 56.4 | 23.7 | 9.7 | 39.8 |
7 | -13,9 | 30 | 57,9 | 24,5 | 10.2 | 40,9 |
8 | -13.3 | 31 | 59.3 | 25.4 | 10,8 | 42 |
9 | -12.8 | 31,9 | 60.8 | 26.2 | 11.4 | 43.1 |
¿Qué es (EE. UU.) RT? El término tonelada de refrigeración se usa comúnmente, y se usa principalmente, en América del Norte. Es una unidad de medida para la capacidad de enfriamiento de una máquina de refrigeración. Tiene algunas variantes, y a veces se le llama una tonelada de refrigeración o simplemente RT para abreviar. El término tonelada de refrigeración es un poco... | -12.2 | 32.8 | 62.3 | 27.1 | 12 | 44.3 |
11 | -11.7 | 33.8 | 63,9 | 28 | 12,6 | 45.4 |
12 | -11.1 | 34.8 | 65.4 | 29 | 13.2 | 46.6 |
13 | -10.6 | 35.8 | 67 | 29,9 | 13.8 | 47.8 |
14 | -10 | 36.8 | 68.6 | 30,9 | 14.4 | 49 |
15 | -9.4 | 37.8 | 70.2 | 31.8 | 15.1 | 50.2 |
dieciséis | -8.9 | 38.8 | 71,9 | 32.8 | 15.7 | 51.5 |
17 | -8.3 | 39.9 | 73.5 | 33.8 | 16.4 | 52.7 |
18 | -7.8 | 40,9 | 75.2 | 34.8 | 17.1 | 54 |
Refrigerante más utilizado en enfriadores: ¿qué refrigerantes se utilizan hoy en día? 1. Agua El uso de agua como refrigerante es una solución de bajo costo que no es tóxica, está fácilmente disponible y es amigable con el medio ambiente. Sin embargo, la elección de refrigerantes a base de agua también tiene importantes desventajas, que incluyen: La temperatura ambiente afecta fácilmente la eficiencia del proceso de enfriamiento En comparación con... | -7.2 | 42 | 77 | 35,9 | 17.7 | 55.3 |
20 | -6.7 | 43.1 | 78.7 | 36,9 | 18,4 | 56,6 |
Cómo elegir el depósito de inercia adecuado | -6.1 | 44.2 | 80.5 | 38 | 19.2 | 57,9 |
22 | -5.6 | 45.3 | 82.3 | 39.1 | 19.9 | 59.3 |
23 | -5 | 46.5 | 84.1 | 40.2 | 20.6 | 60.6 |
24 | -4.4 | 47.6 | 85,9 | 41.3 | 21.4 | 62 |
25 | -3.9 | 48.8 | 87,8 | 42.4 | 22.1 | 63.4 |
26 | -3.3 | 50 | 89.7 | 43.6 | 22,9 | 64.8 |
27 | -2.8 | 51,2 | 91.6 | 44.7 | 23.7 | 66.2 |
28 | -2.2 | 52.4 | 93.5 | 45,9 | 24,5 | 67.7 |
29 | -1.7 | 53.7 | 95.5 | 47.1 | 25,3 | 69.2 |
30 | -1.1 | 54,9 | 97.5 | 48.4 | 26.1 | 70.7 |
31 | -0.6 | 56.2 | 99.5 | 49.6 | 26,9 | 72,1 |
32 | 0 | 57.5 | 101.6 | 50,9 | 27,8 | 73.8 |
33 | 0.6 | 58,8 | 103.6 | 52.1 | 28.6 | 75.3 |
34 | 1.1 | 60.2 | 105.7 | 53.4 | 29.5 | 76,9 |
35 | 1.7 | 61.5 | 107.9 | 54.8 | 30.4 | 78,5 |
36 | 2.2 | 62,9 | 110 | 56.1 | 31.3 | 80.2 |
37 | 2.8 | 64.3 | 112.2 | 57.5 | 32,2 | 81.7 |
38 | 3.3 | 65.7 | 114.4 | 58,9 | 33.1 | 83.5 |
39 | 3.9 | 67.1 | 116.7 | 60.3 | 34.1 | 85.2 |
40 | 4.4 | 68.6 | 118.9 | 61.7 | 35 | 86,9 |
41 | 5 | 70 | 121.2 | 63.1 | 36 | 88,6 |
42 | 5,6 | 71,5 | 123.6 | 64.6 | 37 | 90.4 |
43 | 6.1 | 73 | 125.9 | 66.1 | 38 | 92.2 |
44 | 6.7 | 74.5 | 128.3 | 67.6 | 39 | 94 |
45 | 7.2 | 76.1 | 130.7 | 69.1 | 40 | 95.8 |
46 | 7.8 | 77.6 | 133.2 | 70.6 | 41.1 | 97.6 |
47 | 8.3 | 79.2 | 135,6 | 72.2 | 42,2 | 99.5 |
48 | 8.9 | 80.8 | 138.2 | 73.8 | 43.2 | 101.4 |
49 | 9.4 | 82.4 | 140.7 | 75.4 | 44.3 | 103.3 |
50 | ¿Qué es (EE. UU.) RT? El término tonelada de refrigeración se usa comúnmente, y se usa principalmente, en América del Norte. Es una unidad de medida para la capacidad de enfriamiento de una máquina de refrigeración. Tiene algunas variantes, y a veces se le llama una tonelada de refrigeración o simplemente RT para abreviar. El término tonelada de refrigeración es un poco... | 84.1 | 143.31 | 77.1 | 45.4 | 105.3 |
55 | 12.8 | 92.6 | 156.6 | 106 | 51,2 | 115.3 |
60 | 15.6 | 101.6 | 170.7 | 116.2 | 57.4 | 126 |
sesenta y cinco | 18.3 | 11.3 | 185.7 | 127 | 64 | 137.4 |
70 | 21.1 | 121.5 | 201.5 | 138.5 | 71.1 | 149.3 |
75 | 23,9 | 132.2 | 218.2 | 150.6 | 78.6 | 161.9 |
80 | 26.7 | 143.7 | 235.9 | 163.5 | 86,7 | 175.4 |
85 | 29.4 | 155.7 | 254.6 | 177 | 95.2 | 189.6 |
9o[ | 32,2 | 168.4 | 274.3 | 191.3 | 104.3 | 204.5 |
95 | 35 | 181.9 | 295 | 206.4 | 113.9 | 220.2 |
100 | 37.8 | 196 | 316.9 | 22.3. | 124.1 | 236.8 |
105 | 40.6 | 210.8 | 339.9 | 239 | 134.9 | 254.2 |
110 | 43.3 | 226.4 | 364.1 | 256.5 | 146.3 | 272.5 |
115 | 46.1 | 242.8 | 289.6 | 274.9 | 158.4 | 291.9 |
120 | 48,9 | 260 | 416.4 | 294.2 | 171.1 | 312.1 |
125 | 51.7 | 278.1 | 444.5 | 314.5 | 184.5 | 33.4 |
130 | 54.4 | 297 | 474 | 335.7 | 198.7 | 355.6 |
135 | 57.2 | 316.7 | 505 | 357.8 | 213.5 | 379.1 |
140 | 60 | 337.4 | 537.6 | 380.9 | 229.2 | 403.7 |
145 | 62.8 | 359.1 | 571.7 | 405.1 | 245.6 | 429.6 |
150 | 65,6 | 381.7 | 607.6 | 430.3 | 262.8 | 456.8 |
155 | 68.3 | 405.4 | 645.2 | 456.6 | 281 | 484.8 |
Los puntos de datos se reproducen en función de la información disponible. Nosotros (SCY Chiller) no asumimos ninguna responsabilidad por errores de datos.
Descarga este gráfico aquí.
Hola Leo.
¿Cuál es la presión manométrica del gas r404a en un liofilizador que funciona a una temperatura de -60ºC?
Para el refrigerante R404a a una temperatura de -60ºC, la presión correspondiente suele estar por debajo de su rango operativo habitual. Para encontrar el valor exacto, se debe consultar la tabla de presión-temperatura (PT) específica del R404a. Actualmente no disponemos de esos datos. Sin embargo, recuerde que operar a temperaturas tan bajas puede requerir equipo especializado.